8.8 Standardisation of setpoint / target values
The following table contains details for the standardisation of typical setpoint and actual values. These
details relate to parameters (P400), (P418), (P543), (P546), (P740) or (P741).
Name
Analogue signal
Bus signal
Setpoint values
{Function}
Value
range
Standardisation
Value
range
Max.
value
100% =
-100% =
Standardisation
Limitation
absolute
Setpoint frequency
{01}
0-10V
(10V=100%)
P104 … P105
(min - max)
P104+(P105-P104)
*U
AIN
(V)/10V
±100%
16384 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f
targ
[Hz]/P105
P105
Frequency addition
{02}
0-10V
(10V=100%)
P410 … P411
(min - max)
P410+(P411-P410)
*U
AIN
[V]/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f
targ
[Hz]/P411
P105
Frequency
subtraction
{03}
0-10V
(10V=100%)
P410 … P411
(min - max)
P410+(P411-P410)
*U
AIN
[V]/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f
targ
[Hz]/P411
P105
Minimum
frequency
{04}
0-10V
(10V=100%)
50Hz*
U
AIN
(V)/10V
0…200%
(50Hz=100%)
32767 4000
hex
16384
dec
/
4000
hex
* f
min
[Hz] /
50Hz
P105
Maximum
frequency
{05}
0-10V
(10V=100%)
100Hz*
U
AIN
(V)/10V
0…200%
(100Hz=100%)
32767 4000
hex
16384
dec
/
4000
hex
* f
max
[Hz] /
100Hz
P105
Actual value
Process controller
{06}
0-10V
(10V=100%)
P105*
U
AIN
(V)/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f
targ
[Hz]/P105
P105
Setpoint
process controller
{07}
0-10V
(10V=100%)
P105*
U
AIN
(V)/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f
targ
[Hz]/P105
P105
Torque current
limit
{11}, {12}
0-10V
(10V=100%)
P112*
U
AIN
(V)/10V
0…100%
16384 4000
hex
16384
dec
/
4000
hex
*
Torque [%] / P112
P112
Current limit
{13}, {14}
0-10V
(10V=100%)
P536*
U
AIN
(V)/10V
0…100%
16384 4000
hex
16384
dec
/
4000
hex
*
Current limit [%] /
(P536 * 100)
P536
Ramp time
{15}
0-10V
(10V=100%)
10s*
U
AIN
(V)/10V
0…200%
32767 4000
hex
16384
dec
/
4000
hex
*
Bus setpoint/ 10s
20s
Actual values
{Function}
Actual frequency
{01}
0-10V
(10V=100%)
P201*
U
AOut
(V)/10V
±100%
16384 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f[Hz]/P105
Speed
{02}
0-10V
(10V=100%)
P202*
U
AOut
(V)/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
n[rpm]/P202
Current
{03}
0-10V
(10V=100%)
P203*
U
AOut
(V)/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f[Hz]/P203
Torque current
{04}
0-10V
(10V=100%)
P112* 100/
√((P203)²
-
(P209)²)*
U
AOut
(V)/10V
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
I
q
[A]/(P112)*100/
√((P203)²
-
(P209)²)
Master value
Setpoint frequency
{19} … {24}
/
/
±100%
16384 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
*
f[Hz]/P105
Pos: 673 /Anleitungen/Elektronik/FU und Starter/8. Zusatzinformationen/Normierung Soll- / Istwerte_02 [SK 2xxE, SK 2xxE-FDS] @ 10\mod_1449486572724_388.docx @ 269614 @ @ 1
Speed from
rotary encoder
{22}
/
/
±200%
32767 4000
hex
16384
dec
C000
hex
-
16384
dec
4000
hex
* n[rpm]/
P201*(60/Number
of pairs of poles)