NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
158
BU 0250 en-3021
Pos: 535 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P740 – Prozessdaten Bus In [SK 1x0E, SK 2xxE, SK 500...535E, SK 2xxE-FDS] @ 0\mod_1328175248086_388.docx @ 13313 @ @ 1
P740
[-01]
...
[-19]
PZD bus In
(Process data Bus In)
S
0000 ... FFFF (hex)
This parameter provides
information about the
actual control word and
the setpoints that are
transferred via the bus
systems.
For display, a BUS
system must be selected
in P509.
Standardisation:
(
section 8.8
"Standardisation of
setpoint / target values")
[-01 ] =
Control word
Control word, source from
P509.
[-02] =
Setpoint 1 (P510/1, P546)
[-03] =
Setpoint 2 (P510/1, …)
[-04] =
Setpoint 3 (P510/1, …)
Setpoint data from main
setpoint (P510 [-01]).
[-05] =
res.status InBit P480
The displayed value depicts all
Bus In Bit sources linked with
an "
OR
".
[-06]
= Parameter data In 1
[-07]
= Parameter data In 2
[-08]
= Parameter data In 3
[-09]
= Parameter data In 4
[-10]
= Parameter data In 5
Data during parameter transfer:
Order label (AK), Parameter
number (PNU), Index (IND),
Parameter value (PWE 1/2)
[-11] =
Setpoint 1 (P510/2)
[-12] =
Setpoint 2 (P510/2)
[-13] =
Setpoint 3 (P510/2)
Setpoint data from the master
function value (Broadcast) -
(P502/P503), if P509 = 4
[-14] =
Control word PLC
[-15] =
Setpoint 1 PLC
…
[-19] =
Setpoint 5 PLC
Control word + Setpoint data
from PLC
Pos: 536 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P700-P799/Parameter P741 – Prozessdaten Bus Out [SK 1x0E, SK 2xxE, SK 500...535E, SK 2xxE-FDS] @ 0\mod_1328177890266_388.docx @ 13359 @ @ 1
P741
[-01]
...
[-19]
PZD bus Out
(Process data Bus Out)
S
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.
Standardisation:
(
section 8.8
"Standardisation of setpoint
/ target values")
[-01] =
Status word
Status word, source from
P509.
[-02]
= Actual value 1 (P543)
[-03]
= Actual value 2 (…)
[-04]
= Actual value 3 (…)
Actual values
[-05] =
res.status OutBit P481
The displayed value depicts
all Bus OUT Bit sources linked
with an "
OR
".
[-06] =
Parameter data Out 1
[-07] =
Parameter data Out 2
[-08] =
Parameter data Out 3
[-09] =
Parameter data Out 4
[-10] =
Parameter data Out 5
Data during parameter
transfer.
[-11] =
Actual value 1 master funct.
[-12] =
Actual value 2 master funct.
[-13] =
Actual value 3 master funct.
Actual value of master
function
P502 / P503.
[-14] =
Status word PLC
[-15] =
Actual value 1 PLC
…
[-19] =
Actual value 5 PLC
Status word + Actual values to
PLC
Pos: 537 /Allgemein/Allgemeingültige Module/---------Seitenumbruch kompakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1