NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
124
BU 0250 en-3021
Pos: 387 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P428 – Automatischer Anlauf [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346931806519_388.docx @ 42744 @ @ 1
P428
Automatic start
(
Automatic start)
S
P
0 ... 1
{ 0 }
In the standard setting (P428 =
0
Off
) the inverter requires a flank to enable (signal change
from "low
high") at the relevant digital input.
In the setting
On
1
the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. For this P428 =
1
On
can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.
NOTE:
(P428) not "ON" if (P506) = 6,
Danger!
(See note on (P506))
NOTE:
The "Automatic Start" function can only be used if a digital input of the frequency
inverter (DIN 1 …) is parameterised to the function "Enable Right" or "Enable Left"
and this input is permanently set to "High". The digital inputs of the technology
modules (e.g.: SK CU4 - IOE) do not support this "Automatic Start" function!
NOTE:
The "Automatic Start" function can only be activated if the frequency inverter has
been parameterised to local control ((P509) setting { 0 } or { 1} ).
Pos: 388 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P434 – Digitalausgang Funktion [SK 2xxE-FDS] @ 38\mod_1568386331958_388.docx @ 2559693 @ @ 1
P434
[-01]
[-02]
Digital output function
(Digital output function)
0 ... 40
{ 7 }
[-01] = Digital output 1,
digital output 1 of the FI
[-02] = Digital output 2,
digital output 2 of the FI
Settings 3 to 5 and 11 operate with a 10% hysteresis, i.e. the output delivers (Funct. 11 does not
deliver) when the limit value 24V is reached and switches this off again when a 10% lower value is
undershot (Funct. 11 on again).
This behaviour can be inverted with a negative value in P435.
Setting / function
Output ...
For limit value
or function
(See also P435)
0 =
No function
Low
1 =
External brake, for control of an external 24V brake relay (max. 20 mA). The
output switches at a programmed absolute minimum frequency (P505).
A setpoint delay of 0.2-0.3s (see also P107/P114) should be set for typical
brakes.
Devices with an optional integrated brake rectifier (e.g. Option „-HWR“,
Section 1.7 "Type code / nomenclature ") can control a typical motor brake
directly (
Section 2.3.2.4 "Electromechanical brake")
Low
2 =
Inverter operating
: the output signals voltage at the output
(U-V-W)
.
High
3 =
Current limit
: based on the nominal motor current setting in P203. This value
can be adjusted with scaling (P435).
High
4 =
Torque current limit
: based on motor data settings in P203 and P206.
Signals a corresponding torque load on the motor. This value can be adjusted
with scaling (P435).
High
5 =
Frequency limit
: based on nominal motor frequency setting in P201. This
value can be adjusted with scaling (P435).
High
6 =
Setpoint reached
: indicates that the FI has completed the frequency increase
or decrease. Setpoint frequency = Actual frequency! From a difference of 1Hz
Setpoint
not reached
–
Low signal.
High
7 =
Fault
: general fault message, fault is active or not yet acknowledged.
Fault
-
Low (Ready for operation
-
High)
Low
8 =
Warning
: general warning - a limit value was reached that could result in a
later shutdown of the FI.
Low
9 =
Overcurrent warning
: At least 130 % of the nominal FI current was supplied
for 30 seconds.
Low