1.7 Type code / nomenclature
Pos: 44 /Anleitungen/Elektronik/FU und Starter/1. Allgemeines/Typenschlüssel/Typenschlüssel /Nomenklatur_Ergänzung_Feldverteiler [SK 1xxE-FDS, SK 2xxE-FDS] @ 44\mod_1592908706395_388.docx @ 2636757 @ @ 1
The type code of the device depicts the basic features. A unique identification of the device including
all customer-specific features is only possible via the device’s order or serial number.
Pos: 45 /Anleitungen/Elektronik/FU und Starter/1. Allgemeines/Typenschlüssel/Typenschlüssel /Nomenklatur_Typenschild [SK 1xxE-FDS, SK 2xxE-FDS] @ 11\mod_1463056396244_388.docx @ 320544 @ 3 @ 1
1.7.1 Type plate
All of the information which is relevant for the frequency inverter, including information for identification
of the device can be obtained from the type plate.
( 1 )
Type:
SK 250E-FDS-301-340-A
HWR-HVS-…
Part No.:
5050601-100
ID:
27Q303614961
Version:
AAA
1.0R0
Type:
Type / designation
Part No.:
Order number
ID:
Identification number
Version:
Hardware / Software version
Pos: 46 /Anleitungen/Elektronik/FU und Starter/1. Allgemeines/Typenschlüssel/Typenschlüssel /Nomenklatur_Typenschild_UL- Typenschild [BU 0250] @ 20\mod_1518446782661_388.docx @ 2402906 @ @ 1
( 2 ) Two further plates which contain the supplementary electrical data for UL/CSA are affixed to the
right hand side of the device.
First plate
This warning information is generally attached.
DANGER
-The opening of the branch-circuit
protective device may be an indication that a
fault current has been interrupted.
To reduce the risk of fire or electrical shock,
current-carrying parts and other components,
of the controller should be examined and
replaced if damaged. lf burnout of the current
element of an overload relay occurs, the
complete overload relay must be replaced..
Second plate
The second plate depends on the power plug
connectors which are used.
Amphenol
SCCR:
65 kA, 500 V, BCP Fuse, Class CC, J, T
SCCR:
65 kA, 480 V, BCP CB
SCCR:
20 kA, 500 V, BCP CB
BCP Rating and further Short Circuit Rating
see manual
Suitable for group fusing
SCCR Group Installation:
same except BCP Fuse or CB rated max. 30 A