NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
88
BU 0240 en-US-4920
Pos: 696 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Mel dungen Einschaltsperre (T abellenüberschrift) @ 3\m od_1361803467385_14638.docx @ 59942 @ 5 @ 1
Notifications switch-on block, "not ready"
Display in the
SimpleBox /
ControlBox
Reason:
Text in the ParameterBox
Cause
•
Remedy
Group
Details in
P700 [-03]
Pos: 697 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information I000_01 [SK 180E ... SK 5xxE/SK 500P] @ 2\mod_1347457775195_14638.docx @ 47348 @ @ 1
I000
0.1
Disable voltage from IO
If the "disable voltage" function is parameterized, input
(P420/P480) is Low
• "Set high" input
• Check signal cable (broken cable)
0.2
IO fast stop
If the function "fast stop" is parameterized, input
(P420/P480) is at low
• "Set high" input
• Check signal cable (broken cable)
0.3
Block voltage from bus
• Bus operation (P509): control word bit 1 is "low"
0.4
Bus fast stop
• Bus operation (P509): control word bit 2 is "low"
0.5
Enable on start
Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialization phase (after line power "ON",
or control voltage "ON"). Or electrical phase is lacking.
• Only issue enable signal after completion of
initialization (i.e. when the VFD is ready)
• Activation of "Automatic Start" (P428)
0.6 – 0.7
Reserved
Information message for PLC
see supplementary
instructions
Pos: 698 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information I000_02-Erg änzung 08 und 09 [SK 180E ... SK 5xxE/SK 500P] @ 10\mod_1455725649528_14638.docx @ 306333 @ @ 1
0.8
Right direction blocked
Switch-on block with inverter shut-off activated by:
P540
or by "Enable right block"
(P420
= 31, 73) or "Enable
left block" (
P420
= 32, 74),
The variable frequency drive switches to "Ready for
switching on" status
0.9
Left direction blocked
Pos: 699 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information I006 [SK 180E ... SK 5xxE, auß er SK 500P] @ 2\m od_1347457929759_14638.docx @ 47373 @ @ 1
I006
1)
6.0
Charging error
Charging relay not energized, because:
• Line/DC link voltage too low
• Line voltage failure
• Evacuation run active ((P420)/(P480))
Pos: 700 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information I011 [SK 180E ... SK 5xxE/SK 500P] @ 2\mod_1347457936856_14638.docx @ 47398 @ @ 1
I011
11.0
Analog Stop
If an analog input of the variable frequency drive or a
connected IO extension is configured to detect cable breaks
(2-10 V signal or 4-20 mA signal), the variable frequency
drive switches to the status "ready for switch-on" if the
analog signal undershoots the value
1 V
or
2 mA
This also occurs if the relevant analog input is
parameterized to function "0" ("no function").
• Check connection
Pos: 701 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information I014 "reserviert" [SK 200E ... SK 5xxE/ SK 500P] @ 2\m od_1347457944329_14638.docx @ 47423 @ @ 1
I014
1)
14.4
Reserved
Information message for POSICON
see supplementary
manual
Pos: 702 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information I018 "reserviert" [SK 2xxE/ SK 5xxE/ SK 2xxE-FDS/SK 500P] @ 2\m od_1347457946544_14638.docx @ 47448 @ @ 1
I018
1)
18.0
Reserved
Information message for "Safe stop" function
see
supplementary manual
Pos: 703 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/Information - Kennzeichnung "Nicht ber eit" @ 20\mod_1513067472948_14638.docx @ 2375119 @ @ 1
1) Indication of operating mode (message) on the
Parameter Box
or virtual operating unit of the
NORD CON-Software
:
"Not ready"
Pos: 704 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uch kompakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1
Summary of Contents for NORDAC FLEX SK 205E Series
Page 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Page 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Page 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Page 97: ...Key word index BU 0240 en US 4920 97...
Page 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Page 99: ...Key word index BU 0240 en US 4920 99...
Page 100: ...6072403 4920...