4.2.2.4 Potentiometers P1 and P2 (SK 2x0E size 4 and SK 2x5E)
The setpoint can be set to a fixed value with integrated potentiometer P1. Adjustment of startup and
braking ramps can be made via potentiometer P2.
Potentiometers
P2
P1
Potentiometers
P1
(continuous)
P2
(stepped)
0%
P102/103
P105
-
-
-
10%
0.2 s
10 Hz
1
P102/103
P104
20%
0.3 s
20 Hz
2
0.2 s
2 Hz
30%
0.5 s
30 Hz
3
0.3 s
5 Hz
40%
0.7 s
40 Hz
4
0.5 s
10 Hz
50%
1.0 s
50 Hz
5
0.7 s
15 Hz
60%
2.0 s
60 Hz
6
1.0 s
20 Hz
70%
3.0 s
70 Hz
7
2.0 s
25 Hz
80%
5.0 s
80 Hz
8
3.0 s
30 Hz
90%
7.0 s
90 Hz
9
5.0 s
35 Hz
100%
10.0 s
100 Hz
10
7.0 s
40 Hz
The function of P1 and P2 depends on DIP 4/5. The meaning changes according to the setting.
By default, P1 sets the setpoint value of 0%-100% and P2 sets the ramp from 0.2-7 s.
Pos: 245 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uch kompakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1
Summary of Contents for NORDAC FLEX SK 205E Series
Page 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Page 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Page 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Page 97: ...Key word index BU 0240 en US 4920 97...
Page 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Page 99: ...Key word index BU 0240 en US 4920 99...
Page 100: ...6072403 4920...