6 Operating status messages
BU 0240 en-US-4920
77
Pos: 653 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Diagnose LED s/Diag nose- LEDs am SK 2x0E ( BG 4) und SK 2x5E [SK 2xxE] @ 2\mod_1350999163928_14638.docx @ 49243 @ 355 @ 1
6.2.2 Diagnostic LEDs on the SK 2x0E (size 4) and SK 4x5E
1
RJ12,
RS 232, RS 485
2
Diagnostic LEDs
3
P1/P2, LED-VFD,
LED-ASi
Figure 12: Diagnostic openings SK 2x0E size 4 or SK 4x5E
Status LEDs
LED
Signal
Name
Color
Description
Status
Meaning
DS
dual
red/green
VFD status
off
VFD not on standby,
no line and control voltage
green on
VFD is enabled (VFD running)
green
0.5 Hz
VFD is in standby or not enabled
Flashing
4 Hz
VFD is in switch-on block
red/green
4 Hz
Warning
Alternating
1 Hz
Degree of overload of switched-on VFD
green on +
flashing red
VFD not on standby,
Control voltage available but no line voltage
flashing red
Error, flashing frequency → error number
AS-i
dual
red/green
Status AS-i
Details (
Section
Fehler! Verweisquelle
konnte nicht gefunden werden.
"
Fehler!
Verweisquelle konnte nicht gefunden
werden.
")
SK 2x5E
SK 2x0E
Summary of Contents for NORDAC FLEX SK 205E Series
Page 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Page 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Page 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Page 97: ...Key word index BU 0240 en US 4920 97...
Page 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Page 99: ...Key word index BU 0240 en US 4920 99...
Page 100: ...6072403 4920...