The configurations described below are illustrated in the above diagram:
(1) The “current output” range is smaller than the max. possible measuring range.
(2) The “current output” range is equal to the measuring range:
Scale min.: 4 mA (P16) = tank height – probe H
Scale max.: 20 mA (P17) = tank height – dead zone
(3) The “current output” range is greater than the measuring range:
Scale min.: 4 mA (P16) = 0.0
Scale max.: 20 mA (P17) = tank height – dead zone
(4) The “current output” range is greater than the measuring range:
Scale min.: 4 mA (P16) = tank height – probe H
Scale max.: 20 mA (P17) = tank height
(5) The “current output” range is greater than the measuring range:
Scale min.: 4 mA (P16) = 0.0
Scale max.: 20 mA (P17) = tank height
NOTE: The reference point for distance measurements is the bottom of the flange face.