Hazardous-duty version
Connect the wires of the current loop to terminals 2 and 3 (any polarity). The device is certified to be intrinsically safe may only be used in
conjunction with another intrinsically safe certified equipment. All the allowed electrical safety data indicated on the nameplate must be observed.
An ’Ex’ repeater power supply unit must be used.
For calculation of the supply voltage the same applies as for the standard non-’Ex’
version.
The connected Ex repeater must be HART
-compatible so that it can be operated with
the EView2 communication software or the HART
communicator.
The HART
adapter should be connected to the intrinsically safe input of the Ex repeater!
Units with plastic coating should only be used in IIB gas class hazardous area.
4.3.1.
BUS (HART
®
) communication
MicroTREK has two output options:
Current out. and HART
®
,
Passive, HART
®
protocol
’Ex ia’ current out. and HART
®
Intrinsically safe passive, HART
®
protocol
Both versions compatible with HART
®
protocol, and can be operated with EView2 configuration software or MultiCONT universal process controller (with display!).
In accordance with the Rosemount Standard, HART
®
communication can be used with a MicroTREK 2-wire. It is used as a point-to-point connection between the
MicroTREK 2-wire as slave and the HART
®
master.
N x 4 mA + HART
HART
HHC
-
HART-Master
4…20 mA + HART
Modem
HART
HHC
-
EView2
or HART specific
software and
operating devices