background image

DLCAP

TM

MODULE

 

Data sheet

     

                                                       

MDXE7R5S461PB3111B

 

Nippon Chemi-Con Corporation 

                 

                           

         

32 

 

(2)

 

輸出貿易管理令

Export trade control order (Japanese law) 

輸出貿易管理令により、輸出者がその輸出取引に関連して入手した文書などにより、本製品が大量破壊

兵器等の開発に使用されるなどの情報を得た場合、輸出者が経済産業大臣に輸出許可申請し承認を取る
必要があります。また、上記にかかわらず輸出貨物が大量破壊兵器の開発に使用される恐れがあるとして、経
済産業大臣から「通知」を受けた場合も、輸出者が経済産業大臣に輸出許可申請し承認を取る必要があり
ます。尚、日本ケミコンが「通知」を受けた際は、御社にご連絡致します。

 

Due to the Export Trade Control Ordinance, the documents obtained to the exporter concerning that 

export trade, with information that the product is being used for developing mass destruction weapons, the 
exporter will have to apply and hand in the export permission from the Minister of Economy, Trade and 
Industry.    Also, in spite of the above, if the export items are suspected to be used for developing mass 
destruction weapons, with given “a notice” from the Minister of Economy, Trade and Industry, the exporter 
will still have to apply for export permission from the Minister of Economy, Trade and Industry.    Meanwhile, 
if Nippon Chemi-Con receives “a notice” from Minister of Economy, Trade and Industry, Nippon Chemi-Con 
will contact your company. 

(3)

 

輸送規制

Export control 

国連より危険物輸送に関する勧告に基づき、電気二重層キャパシタの輸送に関し、荷主が遵守すべき最低

限の要求事項及び評価基準が発行されています。詳しくは、危険物輸送に関する国連勧告、

ICAO

技術指

針、

IATA

規則書、

IMO IMDG-Code

の最新版、並びに各国の法律等の最新版を確認いただきますようお願

いします。

 

Regarding the exportation of electric double layer capacitor, a minimum of requirements and evaluation 

criteria for the shippers to perform are issued based on recommendation regarding hazardous material 
transportation from United Nations.    Please confirm UN recommendations regarding hazardous materials 
transportation, ICAO engineering guideline, IATA directory, the newest version of IMO IMDG-Code, and the 
newest version of laws of each country for detail. 

 
 

9-7.  廃棄上の注意事項

Precautions for disposal

 

(1)

 

廃棄方法

How to dispose

 

法令又は地方公共団体などが指定する条例に従った上で、一般産業廃棄物処理業者に廃棄品を渡し、

焼却または埋め立て処理を行って下さい。キャパシタを高温焼却する場合は、焼却前に、全てのキャパシタに穴
をあけてください。

 

Following the laws or ordinances of local public authority, pass the module to an industrial waste dispose, 

and make it operated incinerate or landfill.    Before incineration, please make a hole in the all cells.

 

(2)

 

安全上の注意点

Precautions for safety

 

本モジュールを廃棄する場合は、安全電圧まで放電して下さい。  放電が充分でない状態でキャパシタを潰し

た場合、火花が発生する恐れがあります。この火花による発火等のトラブルを防ぐため、容易に着火する可燃性
ガスや、ガソリンやアセトン等の引火性液体がキャパシタ近傍に無い状態で作業を行って下さい。

 

Before disposal, please discharge the module to safety voltage.    If you crush the module without 

sufficient discharge, there is a risk of sparking.    To prevent the trouble from this spark such as fire 
generation, please perform disposal operation at the environment where flammable liquid such as 
combustible gas or acetone does not exist near the module.

 

 

Summary of Contents for DLCAP

Page 1: ...2 Reference Specification Model Name DLCAPTM MODULE Product Number MDXE7R5S461PB3111B Nippon Chemi Con Corporation Japanese notation has priority over English notation if any doubt arises between Japa...

Page 2: ...mounted inside user system and not supposed to be exposed directly to rain wind sunlight dust etc Charge discharge causes the self heat generation inside the cells in the module Please consider coolin...

Page 3: ...re sensor 14 4 Mechanical specification 16 4 1 Mechanical specification of the module 16 4 2 Appearance 17 4 3 Label figure 18 4 4 Fixing and connection of the module 19 4 5 Packing specification of t...

Page 4: ...equipment is 3pcs connection of electric double layer capacitor DLCAPTM hereafter it is called cell in series hereafter this configuration is called module 2 Voltage balance circuit is mounted to prev...

Page 5: ...le 1 1 Please disconnect the short cable when the module is used The short cable has a short cable attention tag 2 I F RETURN Figure 3 4 2 Please remove I F connector RETURN when modules are connected...

Page 6: ...ist of the module accessories No part name No of pcs Parts appearance Connecting bus bar 1 Fixation screw for connecting plate 3 8 PT 8 Connecting plate 2 3 The above three points are accessories that...

Page 7: ...shown in Figure 2 3 DLCAPTM cell Figure 2 2 Block diagram Power terminal Balance Failure detection circuit substrate C3 C2 C1 Thermistor Power terminal I F Connector IN I F Connector OUT Thermistor H...

Page 8: ...at max charge Nominal capacitance 466 F 10 15 396 to 512 F initial measurement condition 20 10 A DCIR 4 2 m or less initial measurement condition 20 charge open 10 A 1 Sec Dielectric voltage AC 2 5 kV...

Page 9: ...ET turns on and current flows on balance resistance to control cell voltage increase Item Specification Note Balance circuit setup voltage 2 4 V 2 5 2 34 to 2 46 V Balance circuit current 104 7 mA 5 c...

Page 10: ...ormal state is short Abnormal state is open If over voltage 2 94V or higher is detected from either of 3 cells it transmits the anomalous occurrence to outside system by changing the state of photo MO...

Page 11: ...e of the single device AC Output side load voltage peak AC 60 V Output side maximum output loss 500 mW Output side maximum on resistance 2 5 ON On resistance MAX 3 1 3 ON One module per 3 cells series...

Page 12: ...of I F connector IN shows SHORT state through photo MOS relay when I F Connector RETURN is connected to I F Connector OUT at normal operating condition It shows OPEN state at abnormal operating condit...

Page 13: ...er module as Figure 3 4 when you connect 2 modules Overvoltage detection circuit works in the same way when 3 or more modules are connected 2 1 3 I F Connector OUT I F Connector RETURN 3 3 2 2 1 1 I F...

Page 14: ...tics of the thermistor Item Specification Note Sensor model No 103AT SEMITEC SEMITEC Corporation Connector model No PALR 02VF J S T MFG CO LTD PAP 02V S JST Correspondence connector specification PAP...

Page 15: ...esistance 40 188 5 k 30 111 3 k 20 67 77 k 10 42 47 k 0 27 28 k 10 17 96 k 20 12 09 k 25 10 00 k 30 8 313 k 40 5 827 k 50 4 160 k 60 3 020 k 70 2 228 k Table 3 6 Resistance Temperature Table 3 5 Resis...

Page 16: ...cover material PC PBT GF30 Holder Pillar material PBT GF30 UL94V 0 Flame retardant grade UL94V 0 Cell connection method Connect cell terminals with bus bars then fix with screw JIS A5052 H34 Bus bar...

Page 17: ...DLCAPTM MODULE Data sheet MDXE7R5S461PB3111B Nippon Chemi Con Corporation 17 4 2 Appearance Figure 4 1 Outline of the module Rating label Short cable 6 Module fixing holes total 6 spots...

Page 18: ...E Data sheet MDXE7R5S461PB3111B Nippon Chemi Con Corporation 18 4 3 Label figure 1 Rating label figure Figure 4 2 Outline of the rating label Model code Rated voltage and nominal capacitance initial S...

Page 19: ...is module to user system Refer to Figure 4 1 recommended screw size M5 4 8 3 Nm 10 Please select appropriate type and length of the fixation screws to fit user system and fix with appropriate torque T...

Page 20: ...connect plural modules with attached parts as shown Figure 4 3 No Part name No of pcs Note Connecting bus bar 1 3 8 PT Fixation screw for connecting plate 8 0 6Nm 10 Recommended tightening torque 0 6N...

Page 21: ...orporation 21 4 5 Packing specification of the module 1 Packing specification of the module 2 Packing specification of the accessories Figure 4 4 Outline of the packing specification of the module Fig...

Page 22: ...Resistance Change Table 3 1 1200 1200 of the value given in Table 3 1 Load Life Test 70 2 000 20 After the modules are subjected to the rated DC voltage at 70 for 2 000 hours the following specificati...

Page 23: ...ata sheet MDXE7R5S461PB3111B Nippon Chemi Con Corporation 23 7 Environmental protection EU RoHS This product corresponds to RoHS of EU 2013 12 6 Corresponds to exclusion of 6 regulated materials Confi...

Page 24: ...ion should be all right after the test 2 Heat shock 40 6 r 70 6hr 1 20 Following test is done 20 cycles 40 deg C 6hours and 70 deg C 6hours is determined as 1 cycle here Appearance module specificatio...

Page 25: ...eleration rate 1G frequency range 5 200Hz log sweep 10min vibration period each 1 5hour x 3axis XYZ total 4 5hour Appearance module specifications screw torque and circuit operation should be all righ...

Page 26: ...rrow on the top cover points upward See figure below Please contact us for installation at an angle exceeding horizontal 2 Temperature characteristics heat generation Electric double layer capacitor c...

Page 27: ...degradation or failure No protection circuit against over or reverse voltage is installed in this module Please consider to add protection circuit at user system if necessary in case abnormal voltage...

Page 28: ...fore please take care especially when a number of capacitors are connected in series and stored It is recommended to short circuit between terminals and store for safety 4 Environment to avoid Please...

Page 29: ...firm polarity to avoid reverse connection 3 Caution for drop Please do not drop the module Please do not use the module once it has been dropped on the floor 4 Prohibition of deformation Please do not...

Page 30: ...pection 9 5 Please carry out periodic inspections for the module that has been for industrial application Please refer to 9 5 Maintenance inspection for inspection contents 3 Abnormal state a If the m...

Page 31: ...elmet for inspection b Before inspection turn off the power of the equipment and discharge the module voltage to safe level c 0V Voltage of electric double layer capacitor increases by restriking volt...

Page 32: ...MDG Code Regarding the exportation of electric double layer capacitor a minimum of requirements and evaluation criteria for the shippers to perform are issued based on recommendation regarding hazardo...

Page 33: ...2370C Safety Application Guide for fixed electric double layer capacitors 2 Guidelines of the transport of fixed electric double layer capacitors for use in electric and electronic equipment Contact...

Reviews: