SETTINGS OF THE AUTOMATIC FUNCTIONS
Automatic closing
Automatic closing is set on the S2 selector.
The closing times can be set on a value between 0 and 240 seconds.
Special function:
if there is a photoelectric barrier, the time
is reduced by 5 seconds after passage.
Time setting
0
Automatic closing disabled
1
5
seconds
2
10
seconds
3
20
seconds
4
30
seconds
5
45
seconds
6
60
seconds
7
90
seconds
8
120
seconds
9
240
seconds
5
4 6
3
7
2
8
1
90
S2 wobble switch
Reversing function
DIP 4 = ON
The door blocks and reverses its direction for
about 50 cm if the sensitive edge is enabled
during the downward movement.
DIP 4 = OFF
The door blocks and reaches the upper final
position if the sensitive edge is enabled during the
downward movement.
Automatic adaptation to the ground
DIP 2 = ON
This function can be used if there is an SBA
sensor.
Advance notice traffic lights
DIP 3 = ON
With this function the red traffic lights
(terminals 1+2) begin to flash 3 seconds
before closing of the door.
Meaning of display messages
Upper segment:
flashing --> upper final position setting in progress
ON --> upper final position setting completed
Lower segment:
flashing --> lower final position setting in progress
ON --> lower final position setting completed
movement UP,
movement DOWN,
upper final
position,
preliminary limit
lower final
switch
,
position.
Error 3
sensitive edge tripped, for
example
In normal operating conditions, the
status of the door and/or the number
of the error present are shown on the
display.
Operation functions
In normal operating conditions, the
door status and/or the error present are
shown on the display.
Put all of the DIP switches on "OFF".
Fault display (represented with flashing):
1
Safety circuit
2
Lower sensitive edge fault
3
Lower sensitive edge tripped
4
Lower final position not reached (time limit)
5
Upper final position not reached (time limit)
6
Incorrect direction of rotation of gearmotor
7
Power during lifting deactivation
8
Door in the safety limit switch sector
9
The door is not in one of the final positions
correction of the final position is impossible
0
Digital limit switch error
DIP switch functions on main board:
DIP 1 “ON“ and 2, 3, 4 “OFF“
Setting of the final positions
DIP 1, 2, 4 “ON“ and 3 “OFF“
Precision setting of the final position
(increase)
DIP 1, 3, 4 “ON“ and 2 “OFF“
Precision setting of the final position
(decrease)
WARNING:
It is possible to lengthen the duration of the waiting time of a factor
by choice (with selector in position 6 to 9) using the K5 module. The
parameter to be used is P28.