Table 3. SmartCNX Controller - Troubleshooting
Display
Condition
Description
Alert, Error or
Fault
Possible Causes
Solutions
ERROR 1
DIRECTION
ERROR
SmartCNX
Controller detects
operator ran in
wrong direction.
Limit sensor plugs switched on drive
module.
1. Switch limit sensor
plugs or reset
operator handing
Left Hand/Right
Hand.
2. Press RESET to clear
fault.
ERROR 3
Hy5B FAILED*
SmartCNX
Controller detects
communication
error with a Hy5B
vehicle detector.
Caused by Hy5B removal or socket
connection integrity.
1. Press RESET.
2. Remove and re-
install Hy5B.
3. Replace Hy5B, if
needed.
ERROR 4
PRIMARY-
SECONDARY
COM
SmartCNX
Controller detects
a communication
error between
primary and
secondary in
a dual gate
installation.
Several possible causes:
z
Primary/Secondary communication
cable is installed incorrectly.
z
Primary/Secondary not configured
properly through Installer Menu.
z
Operator is not properly earth
grounded.
z
Primary/Secondary communication
cable installed in same conduit as
high-voltage AC power.
z
One operator is powered off.
z
Different software versions between
operators. Check software version
currently loaded in operator by
pressing RESET.
1. Correct
communication
cable.
2. Verify one operator
is set as Primary and
the other is set as
Secondary.
3. Install ground rod
per NEC/NFPA
standard.
4. Install
communication
cables in a low
voltage conduit.
5. Ensure AC power
is present at both
operators and all
power switches are
On.
6. Make sure both
operators are
running same
software version.
TROUBLESHOOTING/ALERTS/FAULTS/ERRORS
* Message indicates which detector the alert applies to: Exit Loop (ELD), Inside Obstruction Loop (IOLD),
Outside Obstruction Loop (OOLD), or Center Loop (CLD).