27
11 - PROGRAMMING BUTTONS
Static:
Set sensitivity to constant force on a scale of 1 to 10 (1 being the most sensitive).
Dynamic:
Set sensitivity of sudden impact force to the moving gate on a scale of 1 to 10 (1 being most
sensitive).
ESC:
Exit the FORCE menu.
11.1 - Force
11.2 - Speed
Max:
Sets the limit of maximum allowed gate speed on a scale of 20% to 100% (20% being the lowest
setting).
Standard:
Sets the limit of the gate speed during normal movement (not soft start/stop) on a scale of
20% to MAX (20% being the lowest setting).
Low:
Sets the limit of the gate speed while in LEARNING mode and when moving in SLOW, on a scale
of 20% to 100% (20% being the lowest setting).
Slowdown:
Set gate speed when going into approaching the open or close limits on a scale of 20% to
100% (20% being the lowest setting).
Max:
Sets the limit of gate acceleration when reversing the gate after an obstacle has been detected by
the UL/Edge or current sense feature (Force). Settings from 3 to 10, with 10 being the highest rate of
gate acceleration.*
Standard:
Sets the limit of the gate acceleration in normal operation. Settings from 1 to MAX, with MAX
being the highest rate of gate acceleration.
**TO PREVENT DAMAGE TO THE GATE OR THE CONTROLLER USE LOWER ACCELERATION
SETTINGS FOR HEAVIER GATES.
ESC:
Exit the SPEED menu.
11.3 - Acceleration
Auto Close:
Sets the timeout before the gate closes automatically from the fully open position. Set-
tings from 0 (off) to 90 seconds. Setting this to 0 will disable the auto close timer.
Slave:
Sets the delay for opening the slave gate leaf in a Master/Slave (Motor 1 and Motor 2 opera-
tion), (dual gate) system. Settings from 0 to 5 seconds with a step of 0.5 seconds.
Lamp/Strobe:
Sets the amount of time the Lamp accessory output is activated prior to gate move-
ment. Settings from 0 to 5 seconds with a step of 0.5 seconds.
Lock:
Sets the amount of time the Magnetic Lock accessory output is activated to disable the lock
when opening the gate. Settings from 0 to 5 seconds with a step of 0.5 seconds.
Run Time: Sets the maximum run time for the gate. Used in case the gate doesn’t reach its limits. Set-
tings from 15 to 120 seconds with a step of 1 second.
ESC:
Exit the DELAY menu.
11.4 - Delay