20
NIBE BA-SVM 10-200
Docking the indoor unit
Docking during use without heat pump
Connecting cold and hot water
The BA-SVM 10-200 unit is not equipped with a shut-off
valve for the central heating system, hot water system
or electric additional heat; these must be installed on
the outside of the indoor unit to facilitate any future ser-
vicing.
It is not necessary to change the configuration of the
hydraulic connections for the indoor unit to work in-
dependently without the outdoor unit.
The hot water tank should be connected to a water
supply system with water pressure of min. 1 bar,
max. 10 bar. If the pressure at the cold water inlet to
the tank is higher than the permissible level, use a
pressure reducer. During heating of the water in the
tank, the pressure increases, which is why each tank
must be equipped with the appropriate safety valve,
installed on the cold water supply, which will protect
the tank against an excessive increase in pressure.
If using hot water circulation, see subsection “Hot
water circulation”.
Installation alternative
P
P
P
-BT6
P
P
P
CAUTION
It is forbidden to install any constrictors (e.g. reduc-
ers, particle filter, etc.) and shut-off valves between
the storage tank and the safety valve. Only fitting a
tee with a draining valve and a tee with an expansion
vessel is permitted.
CAUTION
It is absolutely necessary to install a properly selected
safety valve on the cold water supply pipe.
CAUTION
Do not use the appliance if the safety valve is blocked.