PROGRAM SETTINGS
Activating AXC 40 can be performed via the start guide or
directly in the menu system.
START GUIDE
The start guide appears upon first start-up after heat pump
installation, but is also found in menu 5.7.
MENU SYSTEM
If you do not make all settings via the start guide or need to
change any of the settings, this can be done in the menu
system.
Menu 5.2.4 -accessories
Activating/deactivating of accessories.
Select: "external energy meter".
Menu 5.3.21 - flow sensor / energy meter
Here, you make settings for the external energy meters.
Activated
Setting range: Off/On
Set mode
Setting range: Energy per pulse / Pulses per kWh
Energy per pulse
Setting range: 0 – 10000 Wh
Pulses per kWh
Setting range: 1 – 10000
Up to eight electricity meters or energy meters (BE9-BE16)
can be connected to AXC 40.
Energy per pulse: Here you set the amount of energy to
which each pulse will correspond.
Pulses per kWh: Here, you set the number of pulses per kWh
that are sent to AXC 40.
Caution
Also see the Installer Manual for the main product.