PROGRAM SETTINGS
Activating AXC 40 can be performed via the start guide or
directly in the menu system.
START GUIDE
The start guide appears upon first start-up after heat pump
installation, but is also found in menu 5.7.
MENU SYSTEM
If you do not make all settings via the start guide or need to
change any of the settings, this can be done in the menu
system.
Menu 5.2 - system settings
Activating/deactivating of accessories.
Select: "step controlled add. heat".
Menu 5.3.6 - step controlled add. heat
Here you can perform the following settings:
•
Select when the addition is to start.
•
Set max permitted number of additional steps.
•
If binary stepping is to be used.
Caution
"start additional heat" in the menus 5.3.6 (external)
and 4.9.3 (internal) are factory set at 400DM. If
both the additional heat options are used and you
want to have more steps, the start difference
needs to be changed in one of the menus.
Menu 5.6 - forced control
Forced control of the different components in the heat pump
as well as in the different accessories that may be connec-
ted.
EB1-AA5-K1: Activating additional step 1.
EB1-AA5-K2: Activating additional step 2.
EB1-AA5-K3: Activating additional step 3.
EB1-AA5-K4: Activating the circulation pump (GP10).
Caution
Also see the Installer Manual for the main product.
AXC 40 F-series | EN