Ground water system
GENERAL
With AXC 40 a ground water pump can be connected to the
heat pump if the software controlled output (AUX output)
is used for something else.
This connection enables the use of ground water as heat
source. The ground water is pumped up to an intermediate
heat exchanger. An intermediate heat exchanger is used to
protect the heat pump's exchanger from dirt and freezing.
The water is released into a buried filtration unit or a drilled
well.
The ground water pump runs at the same time as the brine
pump.
From software version 8233R2, the groundwater pump can
be controlled with an analogue control signal from 0-10 V.
COMPATIBLE PRODUCTS
•
S1155
•
S1255
PIPE CONNECTIONS
TEMPERATURE SENSOR
•
Temperature sensor, brine supply line (EP12-BT57) is in-
stalled on the supply line to the climate system.
•
Temperature sensor, brine return line (EP12-BT58) is in-
stalled on the return line to the climate system.
LEK
LEK
E
Install the temperature sensors using cable ties, together
with the heat conducting paste and aluminium tape. Then
insulate with the enclosed insulation tape.
NOTE
To prevent interference, sensor cables to external
connections must not be laid close to high voltage
cables.
SYSTEM DIAGRAM
Caution
This is an outline diagram. Actual installations must
be planned according to applicable standards.
EXPLANATION
Ground water system
EP12
AXC 40
AA25
Heat exchanger, groundwater
EP4
Particle filter
HQ40
Groundwater pump
GP3
Heat pump
EB100
Brine sensor, supply line
BT57
Brine sensor, return line
BT58
OUTLINE DIAGRAM WITH GROUNDWATER
SYSTEM
-EP12-GP3
-EP12-HQ40
-EP12-EP4
-EP12-AA25
-EP12
-EB100
-BT57
-BT58