DIP SWITCH
The DIP switch (S2) on the accessory board (AA5) must be
set as follows.
3
2
1
ON
4
7
6
5
8
PROGRAM SETTINGS
Activating AXC 40 can be performed via the start guide or
directly in the menu system.
The main product’s software must be the latest version.
START GUIDE
The start guide appears upon first start-up after heat pump
installation, but is also found in menu 7.7.
MENU SYSTEM
If you do not make all settings via the start guide or need to
change any of the settings, this can be done in the menu
system.
Menu 7.2.1 - Add/remove accessories
Here, you state which accessories are installed for the
compatible product.
To identify connected accessories automatically, select
"Search for accessories". It is also possible to select accessor-
ies manually from the list.
Menu 7.2.20 - Ground water pump (AXC)
Select: "Alarm at min temp" yes/no.
Select: "Min temp groundwater", factory setting: 3°C
Select: "Contr groundwater pump" yes/no.
"Manual speed" yes/no.
"Manual speed", factory setting 75 %.
"Lowest speed", factory setting 30 %.
Here you adjust settings such as activation/deactivation of
alarm, min. temperature and speeds.
Menu 7.5.3 - Forced control
Here you can force control the various components in the
installation. The most important safety functions remain
active however.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function in
any other way may cause damage to the compon-
ents in your installation.
Caution
Also see the Installer Manual for the main product.
AXC 40 S-series | EN
24