CONNECTION OF SENSORS AND EXTERNAL
BLOCKING
Temperature sensor, brine (EP10-BT26)
Connect sensor to AA5-X2:21-22.
24 23 22 21 20 19 18 17 16 15 14 13
AA25
External
BT26
AA5-X2
External blocking (optional)
A contact (NO) can be connected to AA5-X2:23-24 to allow
the function to be blocked. When the contact closes, the
function is blocked.
24 23 22 21 20 19 18 17 16 15 14 13
AA25
External
External blocking
AA5-X2
Caution
The relay outputs on the accessory board can have
a max load of 2 A (230 V) in total.
CONNECTION OF SHUNT MOTOR (EP10-QN41)
Connect the shunt motor (QN41) to AA5-X9:6 (230 V, open),
AA5-X9:5 (N) and AA5-X9:4 (230 V, close).
1
2
3
4
5
6
7
8
9
AA5-X9
1
M
External
AA25
Open
SH +
N
SH -
Close
QN41
DIP SWITCH
The DIP switch (S2) on the accessory board (AA5) must be
set as follows.
ON
1
2
3
4
5
6
7
8
27
AXC 40 S-series | EN
S