Common electrical connection
NOTE
All electrical connections must be carried out by
an authorised electrician.
Electrical installation and wiring must be carried
out in accordance with national provisions.
The main product must be disconnected from the
power supply when installing AXC 40.
•
To prevent interference, sensor cables to external connec-
tions must not be laid close to high voltage cables.
•
The minimum area of communication and sensor cables
to external connections must be 0.5 mm² up to 50 m, for
example EKKX, LiYY or equivalent.
•
AXC 40 must be installed via an isolator switch. The cable
area has to be dimensioned based on the fuse rating used.
•
Mark the relevant electrical cabinet with a warning about
external voltage, in those cases where a component in
the cabinet has a separate supply.
•
AXC 40 restarts after a power failure.
Electrical circuit diagrams are at the end of the chapter for
each connection option.
CABLE LOCK
Use a suitable tool to release/lock cables in terminal blocks.
LEK
1
1
2
2
3
3
1
2
3
3
4
1
2
LEK
1
1
2
2
3
3
1
2
3
3
4
1
2
1
2
MOUNTING
The AXC module (AA25) is a separate, electric control module
and must be mounted on a wall.
Caution
The screw type must be adapted to the surface
on which installation is taking place.
UN
Use all mounting points and mount the module upright, flat
against the wall.
Leave at least 100 mm of free space around the module to
allow access and make cable routing easier during installa-
tion and servicing.
NOTE
The installation must be carried out in such a way
that IP21 is satisfied.
OVERVIEW ACCESSORY BOARD (AA5)
ON
1
2
3
4
5
6
7
8
-X9
-X2
24
20
21
22
23
15
16
17
18
19
10
11
12
13
14
5
6
7
8
9
1
1
N
L
PE
PE
1
2
3
4
5
6
7
8
2
3
4
5
6
7
8
9
2
3
4
-X8
-X4
-X10
-X1
AA5-X2
AA5-X9
AA5-S2
AA5-X4
AXC 40 S-series | EN
6
S