1 - PRODUCT FEATURES
1.1 TECHNICAL DATA
Power supply (Input)
230 Vac
Type of load (Output)
4 X 230 Vac motors
Max load power (Output)
Max 500 W per output
Number of programmable transmitters
30
Receiver frequency RF
433.920MHz
Operating temperature
-10° +55°
Dimensions (Top-M400)
174 X 46 h 35 mm
Dimensions (LB-M400)
310 x 80 h 70mm
1.2 SENSOR MANAGEMENT
The control unit is designed to manage weather sensors to be connected by wire, which if they intervene can
automatically move the motors.
Compatible sensors are:
WIND:
ALARM: the control unit detects a wind speed higher than the one set, for 10 seconds. Then the control unit turns fully
opens the motors (settable function) and disables the reception of remote or wired commands until the alarm is over.
ALARM NOT PRESENT/END OF ALARM: the control unit detects a wind speed lower than the one set, for 60 seconds.
RAIN
ALARM: the sensor detects water: then the control unit close the motors (settable function) and disables the reception of
remote or wired commands until the alarm is over.
ALARM NOT PRESENT/END OF ALARM: the sensitive part of the rain sensor is dry.
SUN
ALARM: the sensor receives direct light for a period of more than 10 minutes: then the control unit close the motors
(settable function) and disables the reception of remote or wired commands until the alarm is over.
ALARM NOT PRESENT/END OF ALARM: the sensor is in the shade or a command is received
ATTENTION:
If more than one sensor is used, there is the possibility that two alarms may intervene which could require conflicting
interventions.
In these situations, the control panel applies a priority according to this order:
- wind sensor
- rain sensor
- sun sensor
Example:
The wind alarm goes off and the motors must open, but the sun is present and the motors should also close.
The control unit gives priority to the wind sensor and then opens. If the wind alarm is over, the sun is still present, the
motors will close.
3