5.3.17 Fan cycle off (FCF)
Display
Description
Defines the inactive period of the evaporator fan while the compressor is switched off.
Considerations
Fan cycle is the fan cycle on (FCO) time + the fan cycle off (FCF) time.
Range
0 to 30 minutes
Global default
1 minute
5.3.18 Alarm delay (Ad)
Display
Description
Defines the maximum time the cooler door can be open before sounding the alarm
buzzer.
Considerations
If disabled, the door switch is also disabled - if so the controller does not detect door
openings therefore, it does not:
• Update the self-learning matrix for door activity.
• Manage the evaporator fan for door activity.
• Sound door alarms if the door is left open.
Range
00 to 30 minutes
Global default
00 (disabled)
5.3.19 Buzzer duration (b1)
Display
Description
Defines the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the controller switches off the
compressor for the duration of RT before starting door open limp home mode.
Considerations
The controller switches off the compressor after the duration defined by alarm delay
(Ad) + buzzer duration (b1 ).
Range
1 to 254 seconds
Global default
60 seconds