While the controller displays the above, the controller is managing the compressor and the fans:
`
The compressor cycles fifteen (15) minutes off, then five (5) minutes on.
`
The fan switches on with the compressor on cycle, then cycles when the compressor is in the
off cycle as set by the FCO (fan cycle on) and FCF (fan cycle off) parameters.
The controller will reboot when the PF1 fault is cleared or fixed.
4.7
Freeze-up protection (888)
Problems with freeze-up protection may occur if the ambient temperature falls below 0°C (32°F) or if the
appliance sensor fails.
Has
the
ambient
temperature dropped
below
dtt
�
freeze
up
protect
��
No
No
Remove appliance
sensor
Yes
Cooling
switched off as
per
specification
Replace
controller
Yes
Change
appliance
sensor
4.8
Refrigeration system failure (rSF) alarms
Refrigeration system failure (rSF) alarms trigger if the set point (SP) temperature is not reached within the
time defined by the compressor runtime (Ct) parameter. Follow the chart to troubleshoot refrigeration
system failure.
Reset alarm ‐ press
Down button once
Yes
Yes
Is the product
freezing?
Replace
sensor
No
Replace
controller
Is the appliance
sensor short
circuit?
No
See
Not cooling
for
further information