ems100
Product Manual, Issue 4
www.nexo.com
Page 51
5.3.14 Defrost interval (dE)
Display
Description
Defines the period between the end of defrost cycle and beginning of the next defrost
cycle. A time-based defrost cycle helps improve evaporator efficiency.
Considerations
In the event of power loss, the defrost interval (dE) is not maintained. The defrost
interval is reset.
If icing up occurs, review the values of the defrost parameters.
Range
0 to 199 hours
Global default
06 hours
5.3.15 Defrost duration (dd)
Display
Description
Defines the maximum time of a defrost cycle.
Considerations
If icing up occurs, review the values of the defrost parameters.
Range
1 to 199 minutes
Global default
15 minutes
5.3.16 Fan cycle on (FCO)
Display
Description
Defines the active period of the evaporator fan while the compressor is switched off.
Considerations
Fan cycle is the fan cycle on (FCO) time + the fan cycle off (FCF) time.
Range
1 to 30 minutes
Global default
30 minutes
All manuals and user guides at all-guides.com