19
diameter be used to line the chimney, the liner
must be
approved for use with Multi Fuel burning.
Flue liner installation
must comply
with
Current National laws, Building Regulations, and any
Rules in force,
also refer to the flue liner manufacturer’s instructions. The flue liner
must be
replaced when an appliance is replaced, unless proven to be recently installed and in good
condition.
The cross-sectional area of the chimney (at its narrowest point)
must comply
with
Current
National and Local Building Regulations and any rules in force.
Generally, the area needed for a
wood-burning stove installation should measure at least 150 mm internal diameter. Please refer to
Current National laws, Building Regulations, and any Rules in Force.
Important note
: The Windermere 5 SE has been tested for smoke exemption so a minimum
internal flue diameter of 125mm can normally be used. *(This
must be
confirmed with HETAS or
Local Authority Building Control and all
Current National laws, Building regulations and any
Rules in Force).
An over-sized chimney is generally hard to keep warm and results in poor draft. In cases where
there is an oversized masonry chimney, it is highly recommended that the chimney be lined using
an appropriate and approved chimney lining system with the correct internal diameter as stated
above.
With respect to the chimney termination, all chimneys
must
terminate in accordance with
Current
National and Local Building Regulations.
Note:
Current National and Local Regulations
also apply with regard to the placement of
chimneys and flues in connection with thatched roofs.
The chimney or flue system
must be
equipped with access doors for inspection and cleaning. The
size of the cleaning door in the chimney must at least equal to that of the cross-sectional area of
the chimney. In the event that a chimney fire occurs resulting from faulty operation or prolonged
use of damp wood fuel, if safely possible close the air vents of the stove completely, evacuate all
persons from the building and contact your local fire department immediately.
3.4.1 Stove Pipe connection.
Refer to: Current National laws, Building Regulations, and any Rules in Force including BS 8303
and BS EN 15287-1:2007 and (Approved Document J England & Wales)
There are two stove flue exits enabling either top or rear venting depending on installation
requirements.
Check that the flue collar adaptor and flue blanking plate rope seals are not damaged and in correct
position. See figures 3.0, 3.1 & 3.2
Top flue exit position.
If using the stove top flue exit, un-screw and remove the 3 flange bolts supplied from the stove top
flue exit position.
Check that the flue collar adaptor rope seal is not damaged and in correct position.
Align the flue collar adaptor to the stove top flue exit position ensuring the 3 flange bolt hole
positions align with the 3 threaded holes to the stove top flue exit position.
Screw each bolt through each flue collar adaptor flange into the threaded holes within the stove
top, evenly tighten the 3 bolts so the flue collar adaptor is securely fastened to the top of the stove.
Summary of Contents for Windermere 5 SE
Page 9: ...9 Fig 1 1 Main grate positioning Fig 1 2 Top steel baffle positioning...
Page 12: ...12 Fig 1 6 Banking bar positioning Fig 1 7 Ash pan positioning...
Page 52: ...52 4 9 Part Identification Windermere 5 SE...
Page 54: ...54 5 0 Declaration of Performance Energy label Product Fiche 5 1 Declaration of Performance...
Page 55: ...55 5 2 Energy Label...