16
Minimum distances between stove and a conventional brick Class 1 Chimney.
See
:
Figure 2A
Refer to Current National laws, Building Regulations, & any Rules in Force, including BS 8303
and BS EN 15287-1:2007 & (Approved Document J England & Wales).
When installing this stove into a conventional class 1 non combustible brick chimney built to
Current National laws, Building Regulations and any Rules in Force
including BS 8303 and BS
EN 15287-1:2007 the clearances between the stove and
non
-combustible chimney
must comply
with
Current National laws, Building Regulations & any Rules in Force
, providing all surrounding
non
-combustible chimney brick walls have a minimum thickness of 200mm the clearance between
the rear & sides of stove can be reduced to 50mm, refer to
Current National laws, Building
Regulations & any Rules in Force.
However, it is
recommended
that the measurement between
the sides & rear of stove to be as large as possible above this dimension, as the efficiency of this
stove is dependent on the clearances as shown in figure 2A.
For all other clearances to a
non-
combustible brick wall and chimney refer to
Current National
laws, Building Regulations, (Approved Document J England & Wales) & any other Rules in Force,
including BS 8303 and BS EN 15287-1:2007.
Contact your local building authority regarding restrictions and installation requirements.
Summary of Contents for Windermere 5 SE
Page 9: ...9 Fig 1 1 Main grate positioning Fig 1 2 Top steel baffle positioning...
Page 12: ...12 Fig 1 6 Banking bar positioning Fig 1 7 Ash pan positioning...
Page 52: ...52 4 9 Part Identification Windermere 5 SE...
Page 54: ...54 5 0 Declaration of Performance Energy label Product Fiche 5 1 Declaration of Performance...
Page 55: ...55 5 2 Energy Label...