2. Rotate the cover latch forward and down until it stops and the cover fully seats into the chassis. Verify that
there are no gaps along the front edge of the cover.
If the cover is not fully seated, you might not be able to slide the SG6000-CN controller into the rack.
3. Optional: Turn the blue plastic latch lock one-quarter turn in the lock direction, as shown on the latch lock,
to lock it.
After you finish
Reinstall the controller in the cabinet or rack.
Reinstall SG6000-CN controller into cabinet or rack
Replace Fibre Channel HBA in SG6000-CN controller
You might need to replace the Fibre Channel host bus adapter (HBA) in the SG6000-CN
controller if it is not functioning optimally or if it has failed.
Verify Fibre Channel HBA to replace
If you are unsure which Fibre Channel host bus adapter (HBA) to replace, complete this
procedure to identify it.
What you’ll need
• You have the serial number of the storage appliance or SG6000-CN controller where the Fibre Channel
HBA needs to be replaced.
If the serial number of the storage appliance containing the Fibre Channel HBA you are
replacing starts with the letter Q, it will not be listed in the Grid Manager. You must check the
tags attached to the front of each SG6000-CN controller in the data center until you find a
match.
• You are signed in to the Grid Manager using a
Steps
1. From the Grid Manager, select
NODES
.
2. From the table on the Nodes page, select an appliance Storage Node.
3. Select the
Hardware
tab.