SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
8
Handling & Unpacking
Lifting or handling MUST only be carried out by trained and qualified personnel. Ensure
that the lifting operation has been properly planned, risk assessed and that all equipment
has been checked by a skilled and competent Health & Safety representative and
effective control measures put in place.
It is the customer’s responsibility to ensure that operators are trained in handling heavy
goods and to enforce the relevant lifting regulations.
Refer to Dimensions & Weight section for system dry weights.
Handling and
Lifting
The SKS Humidifier MUST always be handled and lifted with care and must remain
within its original packaging for as long as possible prior to installation
The SKS Humidifier package may be carried using a fork lift from the underside. Caution
must be exercised to ensure balanced load before lifting.
Lifting of SKS Humidifier MUST always be carried out using the appropriate Neptronic
Lifting bracket.
Lifting sling angle must be greater than 30
˚ to the horizontal.
(Fig. 3)
Unpacking
SKS Humidifier is shipped on a wooden crate.
Ensure packing wooden crate and skid is removed prior to commissioning.
List of
Accessories
Supplied
Two adjustable steam hose collars per steam outlet to connect on the steam output of
the humidifier.
One 10mm compression fitting for water supply inlet.
One strainer (option).
One actuated control valve (option).
One Float and thermostatic steam trap for the condensate return (option).
!
Slide lifting
strap here