SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
13
Stage 2
– Steam Distribution Pipes Positioning & Installation
Steam Pipe Work to Duct Connections
SKS-200-CHP
(Fig. 11)
A single Ø76mm or Ø100mm or Ø125mm feed pipe must be connected to a single
Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm
condensate drain from the main steam supply.
SKS-333-CHP
(Fig. 12)
Two Ø100mm or Ø125mm steam outlets must be connected to two Multi-Steam with
a suitable reduction at the lowest point to allow a Ø15mm condensate drain from the
main steam supply.
If the two Ø15mm condensate pipes are connected, the common condensate drain
must be Ø20mm.
Ø108mm
Insulated pipe
Air duct
Static pressure
+ 50mm
Multisteam
Min. 7° pipe slop
Ø15mm
Total length of steam conduit should
not exceed 5m
Ø22mm
Ø108mm (x2)
Ø133mm
Min. 7° pipe slope
Insulated pipe
Air Duct
Ø15mm
Static pressure
+ 50mm
min
7°
pipe
slop
e
Total length of steam conduit
should not exceed 5m