SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
27
Start Up
Start-up
1. Proceed to the start-up of the Humidifier, as follow:
a) Open the front access door of the humidifier cabinet; make sure that
manual drain valve is closed.
b) Start up the humidifier by pushing
(ON/OFF) button located on the
humidifier control panel.
c) After 5 seconds, water will start to fill.
The water level will slowly rise in the water level sight glass located on the
side of the evaporation chamber.
d) Verify that there is a humidity demand.
Humidity demand is displayed on the humidifier LCD screen.
e) Humidifier LCD screen will display the water level in percentage (%).
When the display is indicating water level at 100%, the water level in the
water level sight glass will be in front of the mark stamped on the bracket.
f) If there is a humidity demand, the control valve will open
From a cold water start, the humidifier will require 5 to 10 minutes to
produce steam.
Humidifier LCD display is indicating water temperature.
g) During normal operation while steam is produced, the water temperature
will be 100
˚C. Water level percentage must not indicate less than 95%.
h) Observe for water and steam leaks.
Safety Test
2. Check the location of the air flow switch in the system and its operation by
stopping the fan.
With no air movement in the air duct, the humidifier will automatically close
the control valve(s).
Drain and Reset
3. Turn the humidifier OFF, by pushing
(ON/OFF) push button of the control
panel.
4. Execute a manual drain, by pushing the
(DRAIN) push button of the
control panel.
A water jet directed on the water level sensor located in the water level sight
glass will start and create bubbles around it.
5. Reset Air flow switch and humidistat(s) to the proper value, if needed.
End
6. Humidifier is ready for normal operation.