Stage 4
– Water Supply Installation
Water supply installation must conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Inlet
Specifications
Neptronic® SKS Humidifier is designed to be used with potable, reverse osmosis,
deionised and de-mineralized water.
Maximum water supply pressure: 70 to 480kPa
Minimum water temperature: +4
˚C
Maximum water tempe40
˚C
Model
Water Inlet
Connection Size
SKS-XXXX
Ø10mm compression fitting (supplied)
Water Supply
Line Installation
To facilitate servicing, a shut off valve (not supplied) must be installed in the water
line, within 1m of the humidifier.
(Fig. 17)
!
Fill valve
(in the humidifier)
Humidifier base
Male threaded
valve connection
Swivel top
Compression
fitting
Water line 3/8'’ (10mm) pipe
(by others)
Shut off valve
(by others)