SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
32
User Adjustment & Diagnostic Mode
To enter to User adjustment & diagnostic menu: Press simultaneously
&
buttons.
Seq
#
Display
Type
Description
Value
01
Reading
Electrical compartment Ambient Temperature
reading
N/A
02
User
adjustment
Water temperature offset user adjustment
Range: from -
10˚C to +10˚C
Default:
0
03
Reading
Water level frequency reading
N/A
04
User
adjustment
Water level offset user adjustment
Range: from -10% to +10%
Default:
0%
05
Reading
Foaming probe value reading
N/A
06
User
adjustment
Drain time user adjustment
Range: from 4 to 16 min
Default:
see below table
07
User
adjustment
Delay to drain out the humidifier from its
remaining water when there is no demand, in
order to prevent bacteria growth
Range: from 1 to 250 Hrs
Default:
72Hrs
08
User
adjustment
Selection of PID control band value.
This option is available in internal mode only.
Range: from 1 to 20%
Default:
5.0%
09
User
adjustment
Selection of proportional gain values.
This option is available in internal mode only.
Range: from 0 to 100
Default:
100
10
User
adjustment
Selection of integral gain values.
This option is available in internal mode only.
Range: from 0 to 100
Default:
100
11
User
adjustment
Selection of differential gain values.
This option is available in internal mode only.
Range: from 0 to 100
Default:
100
12
User
adjustment
Holding temperature of the evaporation
chamber for fast response to demand
Range: from 15 to 90˚C or OFF
Default:
OFF
13
User
adjustment
Anti-freezing temperature for the evaporation
chamber for humidifier to be installed in
weather proof enclosure.
Range: from 4 to 10˚C or OFF
Default:
OFF
14
User
adjustment
Alarm beep, to be selected ON or OFF
Range: ON or OFF
Default:
OFF
15
User
adjustment
Temperature unit scale Celsius or Fahrenheit
Range: Celsius or
Fahrenheit
Default:
Celsius
16
User
adjustment
LCD Display contrast level
Range: from 0 to 40
Default:
25
(legible LCD)
Amb Tmp
40 C
WTR TOFF
100 C
WTR FREQ
8000 Hz
WTR LOFF
100 %
FOAM PRB
207
No Demnd
72 HRS
Hold Tmp
OFF
Anti-Frz
OFF
ALARM
Beep ON
T Unit
CELSIUS
CONTRAST
25
DrnTm Out
5 MIN
Ctl. Band
5 .0 %
PropGain
K
P
=100
IntgGain
Ki=100
DiffGain
Kd=100