Error Code
Function
Self-diagnostic/Action
E351
Abnormal Auto feeder valve (make-up water)
Check the auto feeder valve
E352
High water pressure
Check the auto feeder valve
E353
Abnormal operation: water pressure sensor
Check the water pressure sensor.
E407
Hot water outlet: thermistor open or short
1.
Check the thermistor.
2.
Replace the thermistor.
E421
Cold water inlet: thermistor open or short
1.
Check the thermistor.
2.
Replace the thermistor.
E515
Abnormal PCB
Check the PCB
E517
Abnormal dip switch setting
Check the dip switches on the front panel and PCB.
E594
Abnormal operation: EEPROM
Check the PCB
E615
Abnormal input & memory
Check the PCB.
E740
Abnormal operation: outdoor temperature sensor
(appears only when the outdoor reset curve is
enabled).
1.
Ensure that the outdoor reset curve is configured
properly.
2.
Check the outdoor temperature sensor wiring
connection.
E777
Abnormal operation: LWCO
1.
Check the LWCO wiring connection
2.
Ensure that the system water level is appropriate.
3.
Add make-up water to the system if necessary.
E782
Abnormal Main-Panel communication
Check the PCB.
If any of the above solutions do not resolve the problem with the Boiler, contact Navien’s Technical department at 1-800-519-8794.
There will be error codes displayed on the front panel and recorded on the PCB board (within the unit) of any problems or failures that
occur with the Boiler.
IMPORTANT
To reset the Boiler, either press the [Reset] button on the front panel or disconnect, then reconnect electrical power to the boiler.
Summary of Contents for NCB-180
Page 3: ......
Page 16: ......
Page 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...
Page 139: ...136 NCB Service Manual Version 1 0 7 4 Fan Gas Assembly...
Page 142: ...Memo...
Page 143: ...140 NCB Service Manual Version 1 0 Memo...
Page 144: ...Memo...
Page 145: ...142 NCB Service Manual Version 1 0 Memo...
Page 146: ...Memo...
Page 147: ...144 NCB Service Manual Version 1 0 Memo...
Page 148: ...Memo...