24 NCB Service Manual
Version 1.0
6.
Re-open the manual gas valve and check for leaks.
7.
Open multiple fixtures that have high flow rates, such as
bathtub and shower faucets, to allow the boiler to operate
up to its maximum firing rate.
8.
When the boiler reaches its maximum firing rate, check the
inlet gas pressure reading on the manometer. The gas
pressure must fall within the proper operating range
indicated in the previous page and also in the
specifications on page 17.
4.2.1 Gas Pipe Sizing Tables (Referenced from 2012 National Fuel Gas Code)
These tables are for reference only. Please consult the gas pipe manufacturer for actual pipe capacities.
Maximum Natural Gas Delivery Capacity
in Cubic Feet (ft
3
) per Hour (0.60 Specific Gravity; 0.5” WC Pressure Drop). Contact your gas supplier for BTU/ft
3
ratings. Use 1,000
BTU/ft3 for simplified calculations. This table is recommended for supply pressures less than 6” WC.
Pipe
Size
Length (including fittings)
10'
(3m)
20'
(6m)
30'
(9m)
40'
(12m)
50'
(15m)
60'
(18m)
70'
(21m)
80'
(24m)
90'
(27m)
100'
(30m)
125'
(38m)
3/4"
360
247
199
170
151
137
126
117
110
104
92
1"
678
466
374
320
284
257
237
220
207
195
173
1 1/4"
1,390
957
768
657
583
528
486
452
424
400
355
1 1/2"
2,090
1,430
1,150
985
873
791
728
677
635
600
532
2"
4,020
2,760
2,220
1,900
1,680
1,520
1,400
1,300
1,220
1,160
1,020
2 1/2"
6,400
4,400
3,530
3,020
2,680
2,430
2,230
2,080
1,950
1,840
1,630
3"
11,300
7,780
6,250
5,350
4,740
4,290
3,950
3,670
3,450
3,260
2,890
4"
23,100
15,900
12,700
10,900
9,660
8,760
8,050
7,490
7,030
6,640
5,890
Summary of Contents for NCB-180
Page 3: ......
Page 16: ......
Page 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...
Page 139: ...136 NCB Service Manual Version 1 0 7 4 Fan Gas Assembly...
Page 142: ...Memo...
Page 143: ...140 NCB Service Manual Version 1 0 Memo...
Page 144: ...Memo...
Page 145: ...142 NCB Service Manual Version 1 0 Memo...
Page 146: ...Memo...
Page 147: ...144 NCB Service Manual Version 1 0 Memo...
Page 148: ...Memo...