GT1175 Slide Door Opus Control Wiring and Programming Manual
www.NabcoEntrances.com
P/N C-00391
Rev 8-11-21
SECTION 8.4: Output Settings
Output Setting
Parameter
Terminal
Default
Range
Description
Output 1
Terminal 7
Sensor Monitoring (N.O.)
►
— —
►
No Output
Output 2
Terminal 13 Fully Closed Position
►
Fully Closed Position
►
Output closes when fully closed
Relay Output 3 Relay Output
— —
►
Closing Status
►
Output closes when door is closing
Terminals
►
Opening Status
►
Output closes when door is opening
►
Fully Opened Position
►
Output closes when door fully opened.
►
Error State Output
►
Output closes when error detected
►
Recycle happened
►
Output closes when recycle occurs
►
Electric Strike Lock
►
Set for electric strike functionality (N.O.)
►
Electric Magnetic Lock
►
Set for Mag lock functionality (N.C.)
►
Air lock
►
Set for Air lock functionality
►
Breakout Pass through
►
Output closes when breakout occurs
►
TrmnL H PassThrough
►
Output changes state when input H
changes state
►
Door Sequencing
►
Provision for door sequencing
►
Sensor Monitoring
(N.O.)
►
Normally open Monitoring circuit
(high logic)
►
Sensor Monitoring
(N.C.)
►
Normally closed Monitoring ciruit
(low logic)
►
Bodyguard Output
►
Outputs data for bodyguard sensors and
other
sensors that utilize same data.
►
For Elite N Output
►
For Elite (N) sensor made by Optex.
(Output 1 only)
Open Delay
Timer
N/A
0.4
0.5, 1.0, 1.5 sec
After Unlock Input
Delay time after activation to allow lock to
unlock before the door starts moving.
Only functional if Electric Lock is selected.
Sequence
Delay Timer
N/A
0
0-10, 12, 15, 20, 25
Same as Open Timer
Delay Time before second Door opens when
an output
is being used for Door Sequencing.
Lock Condition N/A
Every Fully Closed
Every Fully Closed
One way/Night Only
Determines when the electric lock engages.