MP SERIES™ Battery Backup System for Traffic Signals: MP2000E System
Volume One: Operating Manual
Page 6-23
6.b.11 MAINTENANCE Submenu
As this menu is normally used by trained and qualified
personnel ONLY, users have the option of creating a password
to access this menu. Instructions on password creation are
presented in Section 6.c.4.2.1.
The factory default password is 1111. If the password is lost
or forgotten, contact Myers EPS MP2000E Technical Support.
Figure 6-14 details the MAINTENANCE Submenu.
FUNCTION
LCD SHOWS
ACTION
PASSWORD
ACCESS
If the MAINTENANCE Menu has been
password protected, the password must
be entered here. Use the UP / DOWN
arrow key with ENTER keys to confirm a
correct Password. Reentry is required if
an error is made entering a password.
BATT TEST
OPTION
Battery Test Option can be verified here.
Battery Test period of 1 to 255 minutes
can be selected here in 1 minute
increments
The MP2000E can be tested to run on
battery for Maintenance purposes.
INV ON / OFF
Inverter can be turned ON or OFF. This
option is available ONLY when the
MP2000E is in BATTERY or STANDBY
Mode
EVENT LOG VIEW
The Event Log with Date & Time is
viewed here in Binary digital format. See
Section 6.b.14 for details
LINE
CONDITIONING
Allows setting of line detection
parameters.
Figure 6-14: Maintenance Submenu