MP SERIES™ Battery Backup System
for Traffic Signals: MP2000E System
Volume One: Operating Manual
Page 6-65
•
Contact C1 thru C6 are the isolated 1-form C contact closures on the MP2000E front
panel.
•
Program I/P Contact is the programmable input contact closure on the MP2000E front
panel.
•
Contact C1 thru C6 and the Program I/P can be configured in Control – Contacts; the
RS232 Hyperterminal menus and in the MP2000E front panel LCD Settings menu.
6.c.6.3.4.1 Remote Control
Figure 6-51: Remote Control on Information Tab
The Remote Control tab is where you can initialize a Self Test or configure the Contacts.
To conduct a Self Test, click the “Initial Self Test” check box in the UPS Testing box, then
click “Apply” button in the lower right. After the test is completed, the results (passed or
failed) will display in the field below the button. (Use Figure 6-51&52 for reference)
Figure 6-52: UPS Testing & “Apply” Button
Self Test runs for the period set in
Configuration – UPS Configuration – Maintenance – Battery Test Options