MP SERIES™ Battery Backup System
for Traffic Signals: MP2000E System
Volume One: Operating Manual
Page 6-52
SETPOINT
DESCRIPTION/REMARKS
DEFAULT
SETTINGS
SETTINGS
RANGE
Number
Name
41
Lo Lmt
Line/Boost to Battery On Battery
Mode:
Detect Low Limit when input voltage
is reduced below this level; transfers
unit to BATTERY mode from either
BOOST mode (when enabled) or LINE
mode
Boost Off
100 VAC
Boost On
90 VAC
90~120 VAC
48
Hi Gap
User Definable Gap (3-7 VAC)
between selectable values for High
Hyst and High Limit
005 VAC
3~7 VAC
49
Lo Gap
User Definable Gap (3-7 VAC)
between selectable values for Low
Hyst and Low Limit
005 VAC
3~7 VAC
Figure 6-33: Parameter Descriptions (continued)
6.c.5 Menu Tutorial
The same procedure is used for accessing and working with options within each of the
submenus. To illustrate these procedures, this section will explain how to change Battery
Test Options.
In the MAIN menu, type 3 and press ENTER. This will bring up the MAINTENANCE menu,
which is shown in Figure 6-34 below.
Figure 6-34: Maintenance Menu