MP SERIES™ Battery Backup System for Traffic Signals: MP2000E System
Volume One: Operating Manual
Page 4-9
4.c Start Up and Testing
NOTE: If the system does not perform as described below, see the
troubleshooting guide in Sections 7.b and 7.c of this manual.
Start Up Procedure Tips
•
The BBS automatically starts up in Standby mode. After the AC line is
qualified (default 30 seconds) the BBS switches to On Line mode.
•
The PTS is a safeguard that causes the cabinet to revert to utility power in
the event of a failure of the BBS or the batteries.
Figure 4-7: Start Up and Testing Step 1: Turn on the Utility Input Line Power