UPS Setting
01: Output voltage
P1
: It’s for program alternatives. There are 16 programs to set up. Refer to the table.
P2 & P3
: are the setting options or values for each program.
P2:
208/220/230/240
02: Output frequency
05: ECO mode enable/disable
12: Hot standby function
enable/disable
14: Charger voltage adjustment
60 Hz,
CVCF
mode
50 Hz,
Normal
mode
DIS/ENA
P2
HS.H
Select
“
Add
” or “
Sub
” to adjust charger voltage. The
voltage range is from 0V(Default) to 9.9V
P3
YES/NO
06: Voltage range for ECO mode
13:
Battery voltage adjustment
15:
Inverter voltage adjustment
ATO
P2
Output Frequency:
50.0Hz/60.0Hz/ATO
(Default)
P2
: Low voltage /
P3
: High voltage
The setting range is from 5% to 10% of the
nominal voltage.
Select “
Add
” or “
Sub
” function to adjust
battery voltage to real figure. The voltage
range is from 0V(Default) to 5.7V,
Select
“
Add
” or “
Sub
” to adjust inverter voltage. The
voltage range is from 0V(Default) to 6.4V
P3
Frequency Mode:
CVCF Mode (CF)/ Not
CVCF (NCF)
03: Voltage range for bypass
07: Frequency range for ECO mode
10: Reserved/11: Reserved
16: Output voltage calibration
P2:
110V to 209V (default: 110V)
P3:
231V to 276V (default: 264V).
P2
50 Hz: 46.0Hz to 48.0Hz (Default).
60 Hz:
56.0Hz to 58.0Hz (Default).
P3
50 Hz: 52.0Hz (Default) to 54.0 Hz.
60 Hz: 62.0Hz (Default) to 64.0Hz.
04: Frequency range for bypass
08: Bypass mode setting
09: Battery backup time setting
When the output voltage can not be detected
(less
than 50VAC), this menu will be reserved, “
”
P2
: It always shows OP.V as output voltage.
P3
: it shows the internal measurement value of the
output voltage, and you can calibrate it by pressing Up
or Down according to the measurement from an
external voltage meter. The calibration result will be
effective by pressing Enter. The calibration range is
limited /-9V. This function is normally used for
parallel operation.
P2
50 Hz:
46.0Hz
(Default) to 49.0Hz.
60 Hz: 56.0Hz (Default) to 59.0Hz.
P2
OPN
: Bypass allowed /
FBD
: Bypass not allowed
000~999/DIS (Default)
P3
50 Hz: 51.0Hz to 54.0Hz
(Default).
60 Hz: 61.0Hz to 64.0Hz (Default).
60 Hz: 61.0Hz to 64.0Hz
(Default).
P3
ENA/DIS
MODEL
6KRT
6KRTL
10KRT
10KRTL
CAPACITY*
6000 VA / 6000 W
10000 VA / 10000 W
INPUT
Voltage Range
Line Loss
110~300Vac @ (0~60%) Load/140~300V @ (60~80%) Load/176~300Vac @(80~100%)Load
Low Line Comeback
Low Line Loss V 10V
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system/56Hz ~ 64 Hz @ 60Hz system
Phase
Single phase with ground
Power Factor
≧
0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240VAC
AC Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system/56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec
Battery mode
100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec
EFFICIENCY
AC mode
> 94%
Battery Mode
> 93%
BATTERY
Type
12 V / 7 Ah
Depending on applications
12 V / 9 Ah
Depending on applications
Numbers
16
16~20
16
16~20
Recharge Time
7 hours recover to 90% capacity
According to external battery pack 9 hours recover to 90% capacity According to external battery pack
Charging Current
1 A ± 10% (max.)
4 A ± 10% (max.)
1 A ± 10% (max.)
4 A ± 10% (max.)
Charging Voltage
(Battery number*13.65 V) ± 1%
PHYSICAL
Rack/Tower
Dimension, DXWXH(mm)
UPS Unit: 600 x 438 x 88 [2U]
Battery Pack: 688 x 438 x 88 [2U]
UPS Unit: 600 x 438 x 88 [2U]
UPS Unit: 600 x 438 x 88 [2U]
Battery Pack: 688 x 438 x 88 [2U]
UPS Unit: 600 x 438 x 88 [2U]
Net Weight (kgs)
UPS Unit: 17/Battery Pack: 48
UPS Unit: 17
UPS Unit: 20/Battery Pack: 48
UPS Unit: 20
Tower
Dimension, DXWXH(mm)
369 x 190 x 688
369 x 190 x 318
442 x 190 x 688
442 x 190 x 318
Net Weight (kgs)
57
13
67
17
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 55dB @ 1 Meter
Less than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
*Product specifications are subject to change without further notice.
o
PM 6000/10000 LCD Online IEC
V e r s i o n : 1 . 0
EN