5.1 IMPACT67-P DI 16
Technical data
No. of inputs ....................................................... 16
Operating voltage of sensor power supply ........ 24 V ± 25% (18 V to 30.2 V) DC
Power supply (module electronics) .................... via sensor power supply
Incorrect Polarity Protection
System interface ................................................. yes
Digital input ......................................................... yes
Sensor power supply US .................................... yes
Inputs
Quantity .............................................................. 16
Polarity ................................................................ PNP
Input characteristic and switch threshold ........... EN 61131-2
Voltage .............................................................. 24 VDC
Sensor supply
Max. total current 9 A (defined by 7/8“)
Supply for sensors .............................................. max. 200 mA for each sensor
Short-circuit protection for sensors..................... Multifuse
............................................................................ up to 100 mA load automatic start-up
............................................................................ from 100 mA load reset required
Profibus
Baud rates .......................................................... 9.6 KBaud to 12 MBaud
............................................................................ 31.25 KBaud is not supported
Protocol .............................................................. Profibus DP to IEC 61158/61784
Operating modes ............................................... Sync Mode and Freeze Mode are supported
ID number ........................................................... 3101 h
Profibus address................................................. 0-99 set by rotary switches
Galvanic isolation .............................................. Between bus and module electronics