Operation
User manual 55530_hdb_en_16
148 / 156
0x4510
(17680)
0x1805
(6149)
0x1805
(6149)
Overflow/Overflow control of analog input
The analog signal is above the
nominal range. Check the limits of
the nominal range.
0x4510
(17680)
0x1806
(6150)
0x1806
(6150)
Underflow/Underflow control of the analog
input
The analog signal is below the
nominal range. Check the limits of
the nominal range.
0x4510
(17680)
0x1807
(6151) –
0x1808
(6152)
0x1807
(6151) –
0x1808
(6152)
Device-specific error code
For further details on this IO-Link
event, please read the IO-Link
device manual.
0x4510
(17680)
0x1809
(6153)
0x1809
(6153)
Overriding an analog output caused by ex-
ternal voltage
Check the installation on the ana-
log output.
0x4510
(17680)
0x180A
(6154)
0x180A
(6154)
Underride of an analog output by external
voltage
Test event about checking a noti-
fication
0x4510
(17680)
0x180B
(6155)
0x180B
(6155)
Overload at the analog output
Test event to check an incoming/
outgoing warning
0x4510
(17680)
0x180C
(6156) –
0x181E
(6174)
0x180C
(6156) –
0x181E
(6174)
Device-specific error code
For further details on this IO-Link
event, please read the IO-Link
device manual.
0x4510
(17680)
0x181F
(6175)
0x181F
(6175)
Test event A
Test event for checking an incom-
ing/outgoing error
0x4510
(17680)
0x1820
(6176)
0x1820
(6176)
Test event B
Check the permitted voltage
range
0x4510
(17680)
0x1821
(6177)
0x1821
(6177)
Test event C
Check the permitted voltage
range.
0x4510
(17680)
0x1822
(6178) –
0x1829
(6191)
0x1822
(6178) –
0x1829
(6191)
Device-specific error code
For further details on this IO-Link
event, please read the IO-Link
device manual.
0x4510
(17680)
0x1830
(6192)
0x1830
(6192)
Overvoltage in the secondary power supply
(Port Class B) UA
Check the permitted voltage
range.
0x4510
(17680)
0x1831
(6193)
0x1831
(6193)
Undervoltage in the secondary power sup-
ply (Port Class B) UA
Check the current consumption of
connected consumers.
0x4510
(17680)
0x1832
(6194)
0x1832
(6194)
Error in the secondary voltage (Port Class B)
UA
Check the current consumption of
connected consumers.
0x4510
(17680)
0x1833
(6195)
0x1833
(6195)
Overload of secondary power supply (Port
Class B) UA
Check the installation. Check the
current consumption of the con-
nected consumer.
0x4510
(17680)
0x1834
(6196)
0x1834
(6196)
Overload in the main power supply
Check the installation. Check the
current consumption of the con-
nected consumer.
0x4510
(17680)
0x1835
(6197)
0x1835
(6197)
Overload at the sensor power supply for a
subordinate device
Check the installation. Check the
current consumption of the con-
nected consumer.
0x4510
(17680)
0x1836
(6198)
0x1836
(6198)
Overload of actuator supply for a subordi-
nate device
Check the installation.
0x4510
(17680)
0x1837
(6199)
0x1837
(6199)
Overload of a digital output
Check the installation. Check the
current consumption of the con-
nected consumer.
0x4510
(17680)
0x1838
(6200)
0x1838
(6200)
Override of a digital output by an external
voltage
Check the installation.
0x4510
(17680)
0x1839
(6201) –
0x18FF
(6399)
0x1839
(6201) –
0x18FF
(6399)
Device-specific error code
For further details on this IO-Link
event, please read the IO-Link
device manual.
0x4510
(17680)
0x4000
(16384)
0x4000
(16384)
Temperature error
Overload
0x4510
(17680)
0x4100
(16640)
0x4100
(16640)
Ambient temperature: General fault
Check the ambient temperature.
0x4510
(17680)
0x4110
(16656)
0x4110
(16656)
Admissible ambient temperature exceeded Localize the heat source.
Channel
Error Type
Extended
Channel
Error Type
IO-Link
Event
code(s)
Meaning
Action