Configuration/settings
User manual 55530_hdb_en_16
126 / 156
8.12 Factory settings
Reset to factory set-
tings - retain I&M data
The
Reset to factory settings
-
I&M data retained
function resets the mod-
ule to its factory settings but retains the I&M data saved in memory.
Proceed as follows:
Click
Connect online
in the TIA portal.
After connection, mark the module in question.
Open the
MVK-MPNIO
module in project navigation.
Double-click
Online & Diagnostics
.
Below the
Functions
tab, click
Reset to factory settings
to open a win-
dow.
Activate the
Retain I&M data
selection.
Press the
Reset
button.
The module is reset to the factory setting.
Reset to the factory
settings - default val-
ues
Tab. 8-44: Reset to factory settings - default values
Reset to the factory
settings - I&M values
Tab. 8-45: Reset to factory settings - I&M values
Setting
Value
IP address
0.0.0.0
Subnet mask
0.0.0.0
Router address
0.0.0.0
PROFINET device name
Empty
I&M values
Value
System ID code
Empty
Place identifier
Empty
Installed date
Empty
Description
Empty
Additional information
Empty