Configuration/settings
User manual 55530_hdb_en_16
128 / 156
Reset to factory set-
tings - delete I&M data
The
Reset to factory settings
-
Delete I&M data
function resets the module
to the factory settings and, at the same time, deletes the I&M data stored in
memory.
Proceed as follows:
Click
Connect online
in the TIA portal.
After connection, mark the module in question.
Open the
MVK-MPNIO
module in project navigation. Double-click
Online
& Diagnostics
.
Below the
Functions
tab, click
Reset to factory settings
to open a win-
dow.
Activate the
Delete I&M data
menu option.
Press the
Reset
button.
The module is reset to the factory setting.