Part Number: 9290312 May/17/2016 15
Machine Operation
CONTROLS/PROGRAMMING/SETTINGS
After the unit is connected to power it will automatically
begin operating. With the doors closed, the temperature of
the cabinet should reach 36°F to 40°F (2°C to 4°C) in about
one hour.
A thermostat located in the evaporator housing on interior
rear of the unit, controls the temperature in the unit. The
factory setting for the control is 4 and maintains about 38°F
(3°C) in the box. Set toward 1 for higher temperatures and
toward 7 for lower temperatures.
Refrigerators defrost automatically with every cycle of the
compressor. The water generated is routed to a pan on the
rear of the unit and is evaporated by the heat given off by
the compressor.
NOTE: During normal operation the evaporator fan may
cycle and/or pulse independently of the compressor.
EVAPORATOR FAN OPERATION
Cooling Cycle
Defrost Cycle
Model
Compressor
ON
Compressor
OFF
Compressor
ON
ND21TS00
(R404A)
ON
ON
ON
TAPS
For best performance do not allow both taps to remain fully
opened for extended periods of time.
TAP #1
TAP #2
• Tap 1 - Regular Coffee
• Tap 2 - Nitrogenized Coffee
Pouring
If coffee does not pour out of taps items to check are;
1. Verify connections to keg and if coffee keg is empty. If
keg is empty follow replacement steps on page 12.
2. If keg has coffee check nitrogen level at nitrogen tank.
• If outlet pressure drops below 85 - 90 PSI or
tank volume is low replace tank and connect as
shown on page 11.
Section 3
Operation