7. TESTING
HARDWARE FUNCTIONAL TESTING
7-7
Table 7-11 ANALOG I/O TEST 4-20mA
ANALOG
OUTPUT
FORCE
VALUE
EXPECTED
AMMETER
READING
(mA)
MEASURED AMMETER
READING
(mA)
EXPECTED
ANALOG INPUT
READING
(Units)
MEASURED ANALOG INPUT READING
(units)
(%)
1
2
3
4
1
2
3
4
0
4
0
25
8
250
50
12
500
75
16
750
100
20
1000
0-1mA
1.
alter the following setpoints:
SETPOINT S12:ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1: 0-1 mA
SETPOINT S12:ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1 MINIMUM:0
SETPOINT S12:ANALOG I/O\ANALOG INPUT1\ANALOG INPUT1 MAXIMUM:1000
(repeat for analog inputs 2-4)
2.
Analog output values should be
±
0.01mA on the ammeter. Measured analog input values should be
±
10 units. Force the analog outputs
using the following setpoints:
SETPOINT S13:TESTING\TEST ANALOG OUTPUT\FORCE ANALOG OUTPUTS FUNCTION: Enabled
SETPOINT S13:TESTING\TEST ANALOG OUTPUT\ANALOG OUTPUT 1 FORCED VALUE: 0 %
(enter desired percent, repeats for analog output 2-4)
3.
Verify the ammeter readings as well as the measured analog input readings. View the measured values in:
ACTUAL VALUES A2:\METERING DATA\ANALOG INPUTS
Table 7-12 ANALOG I/O TEST 0-1mA
ANALOG
OUTPUT
FORCE
VALUE
EXPECTED
AMMETER
READING
(mA)
MEASURED AMMETER
READING
(mA)
EXPECTED
ANALOG INPUT
READING
(mA)
MEASURED ANALOG INPUT READING
(units)
(%)
1
2
3
4
1
2
3
4
0
0
0
25
0.25
250
50
0.50
500
75
0.75
750
100
1.00
1000
Summary of Contents for SR469
Page 7: ......
Page 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Page 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Page 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Page 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Page 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Page 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Page 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...