HARDWARE FUNCTIONAL TESTING
7. TESTING
7-4
7.2.4
MULTILIN 50:0.025 GROUND ACCURACY TEST
The SR469 specification for Multilin 50:0.025 ground current input accuracy is
±
0.5% of CT rated primary (25A). Perform the steps below to
verify accuracy.
1.
Alter the following setpoint:
SETPOINT S2:SYSTEM SETUP\CURRENT SENSING\GROUND CT: MULTILIN 50:0.025
2.
Measured values should be
±
0.125A. Inject the values shown in the table below either as primary values into a Multilin 50:0.025 Core
Balance CT or as secondary values that simulate the core balance CT. Verify accuracy of the measured values. View the measured
values in:
ACTUAL VALUES A2:\METERING DATA\CURRENT METERING
Table 7-5 MULTILIN 50:0.025 GROUND CURRENT TEST
PRIMARY INJECTED
CURRENT
50:0.025 CT
(A)
SECONDARY
INJECTED CURRENT
(mA)
EXPECTED
CURRENT
READING
(A)
MEASURED
GROUND
CURRENT
(A)
0.25
0.125
0.25
1
0.5
1.00
10
5
10.00
25
12.5
25.00
7.2.5
RTD ACCURACY TEST
The SR469 specification for RTD input accuracy is
±
2
°
. Perform the steps below to verify accuracy.
1.
alter the following setpoints:
SETPOINT S8:RTD TEMPERATURE\RTD TYPE\STATOR RTD TYPE: 100 ohm Platinum
(select desired type)
SETPOINT S8:RTD TEMPERATURE\RTD #1\RTD #1 APPLICATION: Stator
(repeat for RTDs 2-12)
2.
Measured values should be
±
2
°
C or ±4° F. Alter the resistances applied to the RTD inputs as per the table below to simulate RTDs and
verify accuracy of the measured values. View the measured values in:
ACTUAL VALUES A2:\METERING DATA\TEMPERATURE
Summary of Contents for SR469
Page 7: ......
Page 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Page 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Page 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Page 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Page 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Page 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Page 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...