6. COMMUNICATIONS
MEMORY MAP
6-29
GROUP
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
CURRENT
1180
Phase CT Primary
1
5001
1
A
F1
5001
SENSING
1181
Motor Full Load Amps
1
5001
1
A
F1
5001
1182
Ground CT Type
0
3
1
-
FC104
3
1183
Ground CT Primary
1
5000
1
A
F1
100
1184
Phase Differential CT Type
0
2
1
-
FC105
0
1185
Phase Differential CT Primary
1
5000
1
A
F1
100
1186
Enable Two Speed Motor Option
0
1
1
-
FC103
0
1187
Speed Two Phase CT Primary
1
5000
1
A
F1
100
1188
Speed Two Motor Full Load Amps
1
5000
1
A
F1
1
1189
Reserved
...
119F
Reserved
VOLTAGE
11A0
Voltage Transformer Connection Type
0
2
1
-
FC106
0
SENSING
11A1
Voltage Transformer Ratio
100
30000
1
-
F3
3500
11A2
Motor Nameplate Voltage
100
20000
1
V
F1
4000
11A3
Enable Single VT Connection
0
1
1
-
FC143
0
11A4
Reserved
...
11BF
Reserved
POWER
11C0
Nominal System Frequency
0
1
1
-
FC107
0
SYSTEM
11C1
System Phase Sequence
0
1
1
-
FC124
0
11C2
Speed2 Phase Sequence
0
1
1
-
FC124
0
11C3
Reserved
...
11C7
Reserved
SERIAL COM.
11C8
Serial Communication Control
0
1
1
-
FC103
0
CONTROL
11C9
Assign Start Control Relays
0
2
1
-
FC137
0
11CA
Reserved
...
11CF
Reserved
REDUCED
11D0
Reduced Voltage Starting
0
1
1
-
FC103
0
VOLTAGE
11D1
Control Relays for Reduced Voltage Starting
0
2
1
-
FC137
2
11D2
Transition On
0
2
1
-
FC108
0
11D3
Reduced Voltage Start Level
25
300
1
% FLA
F1
100
11D4
Reduced Voltage Start Timer
1
500
1
s
F1
200
11D5
Incomplete Sequence Trip Relays
0
3
1
-
FC111
0
11D6
Reserved
...
122F
Reserved
STARTER
1230
Starter Status Switch
0
1
1
-
FC109
0
STATUS
1231
Reserved
...
Summary of Contents for SR469
Page 7: ......
Page 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Page 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Page 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Page 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Page 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Page 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Page 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...