6. COMMUNICATIONS
MEMORY MAP
6-55
GROUP
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
1D1F
Pre-Fault Differential Current
0
110
1
xCT
F3
0
1D20
Reserved
...
1D3B
Reserved
1D3C
Pre-Fault Stator RTD Temperature (in Fahr.)
-58
482
1
0
F
F4
104
1D3D
Pre-Fault Bearing RTD Temperature (in Fahr.)
-58
482
1
0
F
F4
104
1D3E
Pre-Fault Other RTD Temperature (in Fahr.)
-58
482
1
0
F
F4
104
1D3F
Pre-Fault Ambient RTD Temperature (in Fahr.)
-58
482
1
0
F
F4
104
FAULT
1D40
Fault Current Phase A
0
2000
1
x FLA
F3
0
VALUES
1D41
Fault Current Phase B
0
2000
1
x FLA
F3
0
1D42
Fault Current Phase C
0
2000
1
x FLA
F3
0
1D43
Fault Ground Current
0
50000
1
A
F2
0
1D44
Fault Line Voltages
0
110
1
x Rated
F3
100
1D45
Fault Current Lags Voltage
0
120
30
0
F1
0
1D46
Stator RTD Fault Temperature
-50
250
1
0
C
F4
40
1D47
Bearing RTD Fault Temperature
-50
250
1
0
C
F4
40
1D48
Other RTD Fault Temperature
-50
250
1
0
C
F4
40
1D49
Ambient RTD Fault Temperature
-50
250
1
0
C
F4
40
1D4A
Fault System Frequency
450
700
1
Hz
F2
600
1D4B
Fault Analog Input 1
0
100
1
% range
F1
0
1D4C
Fault Analog Input 2
0
100
1
% range
F1
0
1D4D
Fault Analog Input 3
0
100
1
% range
F1
0
1D4E
Fault Analog Input 4
0
100
1
% range
F1
0
1D4F
Fault Differential Current
0
110
1
xCT
F3
0
1D50
Reserved
...
1D7B
Reserved
1D7C
Fault Stator RTD Temperature (in Fahrenheit)
-58
482
1
0
F
F4
104
1D7D
Fault Bearing RTD Temperature (in Fahrenheit)
-58
482
1
0
F
F4
104
1D7E
Fault Other RTD Temperature (in Fahrenheit)
-58
482
1
0
F
F4
104
1D7F
Fault Ambient RTD Temperature (in Fahrenheit)
-58
482
1
0
F
F4
104
TEST OUTPUT
1D80
Force Operation of Relays
0
8
1
-
FC139
0
RELAYS
1D81
Reserved
...
1D8F
Reserved
TEST
1D90
Force Analog Outputs
0
1
1
-
FC126
0
ANALOG
1D91
Analog Output 1 Forced Value
0
100
1
% range
F1
0
OUTPUTS
1D92
Analog Output 2 Forced Value
0
100
1
% range
F1
0
1D93
Analog Output 3 Forced Value
0
100
1
% range
F1
0
1D94
Analog Output 4 Forced Value
0
100
1
% range
F1
0
1D95
Reserved
...
Summary of Contents for SR469
Page 7: ......
Page 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Page 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Page 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Page 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Page 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Page 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Page 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...