1.4520.598 – MIC5 IPE Prim Short Circuit Cyl 9
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 9 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
1.4520.599 – MIC5 IPE Prim Short Circuit Cyl 10
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 10 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
1.4520.600 – MIC5 IPE Prim Short Circuit Cyl 11
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 11 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
1.4520.601 – MIC5 IPE Prim Short Circuit Cyl 12
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 12 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
1.4520.602 – MIC5 IPE Prim Short Circuit Cyl 13
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 13 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
1.4520.603 – MIC5 IPE Prim Short Circuit Cyl 14
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 14 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
1.4520.604 – MIC5 IPE Prim Short Circuit Cyl 15
Red alarm. Initiated by MIC5.
Cause
Corrective action
Short circuit in primary circuit of
cylinder 15 in ignition sequence.
1. Check cabling to ignition coil (→ Page 227).
2. Check ignition coil.
108 | Troubleshooting | MS150116/04E 2018-04